Pick out the detectors whose readings never move while the ledger says normal, and hand them back to maintenance
For Production roles at Manufacturing companies, and for the equipment and safety staff who run alarm inspections, keep the ledger, and file repair requests. It solves the ledger-says-normal-but-the-reading-never-moves problem: find those devices first, confirm on site whether the device failed or nobody filed the repair, then decide repair or replace.
State how long a reading can stay unchanged before it is suspect, and which record source to compare against. The source material cites one case of 23 days unchanged; the actual threshold should follow the device type and your own inspection cycle, written into the check rules before enforcement.
Match the detectors' historical readings against the ledger's normal entries by device tag number, flag entries where readings stay flat for a long stretch or disagree with the ledger's verdict, and build a to-verify list.
Trigger every entry on the list once on site: does the audible-visual alarm fire, does the sensor respond. Then judge whether the sensor failed, the wiring broke, or someone muted or cut power on purpose. Never conclude from data alone.
Each entry records the device tag, how it was found, the on-site conclusion, the matching repair order number, and the owner. No repair order? Either open one retroactively or leave an approved do-not-fix-yet note.
Before issuing each new list, check every prior entry: repaired, or a clear disposition on record. An entry appearing two cycles in a row gets flagged separately, so the list does not keep growing while nobody follows up.