Compare setting sheets item by item for production teams, and cut the misses of manual checking
For production roles in energy and utilities: any scenario where relay protection setting sheets must be checked item by item across the notification sheet, the field devices, and the archived records. The source notes that procedures require control words to be identical and other settings within a 1% tolerance, and that manual item-by-item comparison is prone to misses.
Split the setting sheet into control words and other settings, and specify the comparison source and rule for each: control words are judged as 'must be identical', other settings by the sub-1% tolerance the source cites.
Before comparing, confirm the notification sheet, field devices, and archived records agree on version number and date. If they disagree, pause the comparison and first establish which copy is the currently valid version.
For each mismatch, record the item name, both values, the rule applied, and who confirmed it. The source cites an incident where the field read 3Ω against 0.33Ω on the notification sheet; flag differences of that magnitude separately and recheck them first.
The tool only outputs a difference list; qualified personnel make the final call. If the rules or the field scope change, record what changed and when it takes effect, so the old rules do not keep running.
Before go-live, run the tool on historical setting sheets already confirmed correct, and check that it reproduces the same item-by-item differences a human found. Chase down every unmatched item before daily use.