Help production staff explain the gaps in the PUE monthly report's breakdown, without having to back-calculate to make the numbers fit
Aimed at production staff in the information technology and internet industry who fill in energy-consumption data, and the managers who need to sign off on the monthly report. It mainly addresses the problem of back-calculating to make numbers fit when sub-metering is incomplete, so the reported figures don't reconcile with the books. The source lists it as an industry-specific solution and Live, but gives no threshold for applicable scale; whether it suits both small server rooms and large data centers has to be judged against your own metering conditions.
List every meter — the main meter, IT equipment, cooling, power distribution losses, and so on — with its installation location, measuring range, and reading method, and mark which readings are actual and which are estimated. Without this step, you can't tell where the gaps are when you back-calculate later.
In the monthly report, give the parts without sub-metering their own row labeled 'unmetered or estimated', stating the estimation method and share, and don't fold them into the measured breakdown. Let the reviewer see at a glance which part was derived and which was read from a meter.
When back-calculation is really needed, put the main-meter reading, the sum of the measured sub-items, and the difference calculation on the same sheet, noting the reading date and the person who took it. If questioned later, you can recalculate the result using the same method.
Write the definitions of the PUE numerator and denominator, the statistical period, and how mains power and UPS losses are allocated into a fixed note, and carry it across months. If you change the method midway, note the month and the reason in the monthly report, otherwise the year-over-year figures aren't comparable.
Agree to read the meters at the same time each month, and record any earlier or delayed reading due to holidays. Drifting reading times make the cooling sub-item swing high and low around seasonal changes, which looks like an equipment fault.