For existing data halls: a way to tune the cooling plant without downtime, saving power and inspection labor
A good fit for existing data centers that already have cooling plant equipment and basic monitoring, high rack density, and electricity as the largest operating cost — especially Tier-A/Class-A halls that cannot shut down for retrofit. The source lists the industry as IT & Internet; the subject is a Class-A third-party data center in South China with roughly 1,000 racks. The roles are data hall operations and infrastructure leads, and the problem is that every bit of PUE reduction is hard-won and tuning relies on human experience.
Points for chillers, pumps, cooling towers and end-state temperature/humidity must be brought in first; with one data stream missing, load prediction and optimization later have no basis. Check each point against the actual equipment before go-live — do not enter automatic regulation until this step is done.
The model predicts cooling load for the coming period, picks a more power-efficient combination from all available equipment, and sets the supply water temperature. People used to decide from experience how many chillers to run and what water temperature; now the model computes and people review.
Constraints like temperature/humidity limits, equipment start/stop counts and minimum standby units are written as rules by operations; AI only issues commands within them. Anything beyond the bounds reverts to human confirmation — better to skip one adjustment than touch the compliance red line.
Shift-based manual meter reading and walk-throughs are replaced by a unified alarm center watching for anomalies; people move from scheduled inspection to handling alarms and reviewing adjustment records. The prerequisite: alarm thresholds set per device on site, otherwise false alarms pile up daily and nobody reads them.
The source's path is no downtime and no chiller retrofit — only adding the data acquisition and control layer. Following that idea, trial on one subsystem of the cooling plant first, confirm regulation does not affect temperature/humidity compliance, then extend to the whole plant.
Case: A Class-A third-party data center in South China (Mushroom IoT client, anonymized at client request; organization name not publicly disclosed) (2026) · vendor-reported
Vendor-reported, single-project sample; measurement method and statistics period not stated — cite with attribution.
Source: https://developer.cloud.tencent.com/article/2759987?policyId=1004